										 |  |  | Generic Thermal Sysfs driver How To | 
					
						
							| 
									
										
										
										
											2009-10-26 08:38:59 +01:00
										 |  |  | =================================== | 
					
						
							| 
									
										
										
										
											2008-01-17 15:51:08 +08:00
										 |  |  | 
 | 
					
						
							|  |  |  | Written by Sujith Thomas <sujith.thomas@intel.com>, Zhang Rui <rui.zhang@intel.com> | 
					
						
							|  |  |  | 
 | 
					
						
							|  |  |  | Updated: 2 January 2008 | 
					
						
							|  |  |  | 
 | 
					
						
							|  |  |  | Copyright (c)  2008 Intel Corporation | 
					
						
							|  |  |  | 
 | 
					
						
							|  |  |  | 
 | 
					
						
							|  |  |  | 0. Introduction | 
					
						
							|  |  |  | 
 | 
					
						
							| 
									
										
										
										
											2009-10-26 08:38:59 +01:00
										 |  |  | The generic thermal sysfs provides a set of interfaces for thermal zone | 
					
						
							|  |  |  | devices (sensors) and thermal cooling devices (fan, processor...) to register | 
					
						
							|  |  |  | with the thermal management solution and to be a part of it. | 
					
						
							| 
									
										
										
										
											2008-01-17 15:51:08 +08:00
										 |  |  | 
 | 
					
						
							| 
									
										
										
										
											2009-10-26 08:38:59 +01:00
										 |  |  | This how-to focuses on enabling new thermal zone and cooling devices to | 
					
						
							|  |  |  | participate in thermal management. | 
					
						
							|  |  |  | This solution is platform independent and any type of thermal zone devices | 
					
						
							|  |  |  | and cooling devices should be able to make use of the infrastructure. | 
					
						
							| 
									
										
										
										
											2008-01-17 15:51:08 +08:00
										 |  |  | 
 | 
					
						
							| 
									
										
										
										
											2009-10-26 08:38:59 +01:00
										 |  |  | The main task of the thermal sysfs driver is to expose thermal zone attributes | 
					
						
							|  |  |  | as well as cooling device attributes to the user space. | 
					
						
							|  |  |  | An intelligent thermal management application can make decisions based on | 
					
						
							|  |  |  | inputs from thermal zone attributes (the current temperature and trip point | 
					
						
							|  |  |  | temperature) and throttle appropriate devices. | 
					
						
							| 
									
										
										
										
											2008-01-17 15:51:08 +08:00
										 |  |  | 
 | 
					
						
							|  |  |  | [0-*]	denotes any positive number starting from 0 | 
					
						
							|  |  |  | [1-*]	denotes any positive number starting from 1 | 
					
						
							|  |  |  | 
 | 
					
						
							|  |  |  | 1. thermal sysfs driver interface functions | 
					
						
							|  |  |  | 
 | 
					
						
							|  |  |  | 1.1 thermal zone device interface | 
					
						
							| 
									
										
										
										
											2009-10-26 08:38:59 +01:00
										 |  |  | 1.1.1 struct thermal_zone_device *thermal_zone_device_register(char *name, | 
					
						
							|  |  |  | 		int trips, void *devdata, struct thermal_zone_device_ops *ops) | 
					
						
							|  |  |  | 
 | 
					
						
							|  |  |  |     This interface function adds a new thermal zone device (sensor) to | 
					
						
							|  |  |  |     /sys/class/thermal folder as thermal_zone[0-*]. It tries to bind all the | 
					
						
							|  |  |  |     thermal cooling devices registered at the same time. | 
					
						
							|  |  |  | 
 | 
					
						
							|  |  |  |     name: the thermal zone name. | 
					
						
							|  |  |  |     trips: the total number of trip points this thermal zone supports. | 
					
						
							|  |  |  |     devdata: device private data | 
					
						
							|  |  |  |     ops: thermal zone device call-backs. | 
					
						
							|  |  |  | 	.bind: bind the thermal zone device with a thermal cooling device. | 
					
						
							|  |  |  | 	.unbind: unbind the thermal zone device with a thermal cooling device. | 
					
						
							|  |  |  | 	.get_temp: get the current temperature of the thermal zone. | 
					
						
							|  |  |  | 	.get_mode: get the current mode (user/kernel) of the thermal zone. | 
					
						
							|  |  |  | 	    - "kernel" means thermal management is done in kernel. | 
					
						
							|  |  |  | 	    - "user" will prevent kernel thermal driver actions upon trip points | 
					
						
							|  |  |  | 	      so that user applications can take charge of thermal management. | 
					
						
							|  |  |  | 	.set_mode: set the mode (user/kernel) of the thermal zone. | 
					
						
							|  |  |  | 	.get_trip_type: get the type of certain trip point. | 
					
						
							|  |  |  | 	.get_trip_temp: get the temperature above which the certain trip point | 
					
						
							|  |  |  | 			will be fired. | 
					
						
							| 
									
										
										
										
											2008-01-17 15:51:08 +08:00
										 |  |  | 
 | 
					
						
							|  |  |  | 1.1.2 void thermal_zone_device_unregister(struct thermal_zone_device *tz) | 
					
						
							|  |  |  | 
 | 
					
						
							| 
									
										
										
										
											2009-10-26 08:38:59 +01:00
										 |  |  |     This interface function removes the thermal zone device. | 
					
						
							|  |  |  |     It deletes the corresponding entry form /sys/class/thermal folder and | 
					
						
							|  |  |  |     unbind all the thermal cooling devices it uses. | 
					
						
							| 
									
										
										
										
											2008-01-17 15:51:08 +08:00
										 |  |  | 
 | 
					
						
							|  |  |  | 1.2 thermal cooling device interface | 
					
						
							|  |  |  | 1.2.1 struct thermal_cooling_device *thermal_cooling_device_register(char *name, | 
					
						
							| 
									
										
										
										
											2009-10-26 08:38:59 +01:00
										 |  |  | 		void *devdata, struct thermal_cooling_device_ops *) | 
					
						
							|  |  |  | 
 | 
					
						
							|  |  |  |     This interface function adds a new thermal cooling device (fan/processor/...) | 
					
						
							|  |  |  |     to /sys/class/thermal/ folder as cooling_device[0-*]. It tries to bind itself | 
					
						
							|  |  |  |     to all the thermal zone devices register at the same time. | 
					
						
							|  |  |  |     name: the cooling device name. | 
					
						
							|  |  |  |     devdata: device private data. | 
					
						
							|  |  |  |     ops: thermal cooling devices call-backs. | 
					
						
							|  |  |  | 	.get_max_state: get the Maximum throttle state of the cooling device. | 
					
						
							|  |  |  | 	.get_cur_state: get the Current throttle state of the cooling device. | 
					
						
							|  |  |  | 	.set_cur_state: set the Current throttle state of the cooling device. | 
					
						
							| 
									
										
										
										
											2008-01-17 15:51:08 +08:00
										 |  |  | 
 | 
					
						
							|  |  |  | 1.2.2 void thermal_cooling_device_unregister(struct thermal_cooling_device *cdev) | 
					
						
							|  |  |  | 
 | 
					
						
							| 
									
										
										
										
											2009-10-26 08:38:59 +01:00
										 |  |  |     This interface function remove the thermal cooling device. | 
					
						
							|  |  |  |     It deletes the corresponding entry form /sys/class/thermal folder and | 
					
						
							|  |  |  |     unbind itself from all the thermal zone devices using it. | 
					
						
							| 
									
										
										
										
											2008-01-17 15:51:08 +08:00
										 |  |  | 
 | 
					
						
							|  |  |  | 1.3 interface for binding a thermal zone device with a thermal cooling device | 
					
						
							|  |  |  | 1.3.1 int thermal_zone_bind_cooling_device(struct thermal_zone_device *tz, | 
					
						
							| 
									
										
										
										
											2009-10-26 08:38:59 +01:00
										 |  |  | 		int trip, struct thermal_cooling_device *cdev); | 
					
						
							| 
									
										
										
										
											2008-01-17 15:51:08 +08:00
										 |  |  | 
 | 
					
						
							| 
									
										
										
										
											2009-10-26 08:38:59 +01:00
										 |  |  |     This interface function bind a thermal cooling device to the certain trip | 
					
						
							|  |  |  |     point of a thermal zone device. | 
					
						
							|  |  |  |     This function is usually called in the thermal zone device .bind callback. | 
					
						
							|  |  |  |     tz: the thermal zone device | 
					
						
							|  |  |  |     cdev: thermal cooling device | 
					
						
							|  |  |  |     trip: indicates which trip point the cooling devices is associated with | 
					
						
							|  |  |  | 	  in this thermal zone. | 
					
						
							| 
									
										
										
										
											2008-01-17 15:51:08 +08:00
										 |  |  | 
 | 
					
						
							|  |  |  | 1.3.2 int thermal_zone_unbind_cooling_device(struct thermal_zone_device *tz, | 
					
						
							| 
									
										
										
										
											2009-10-26 08:38:59 +01:00
										 |  |  | 		int trip, struct thermal_cooling_device *cdev); | 
					
						
							| 
									
										
										
										
											2008-01-17 15:51:08 +08:00
										 |  |  | 
 | 
					
						
							| 
									
										
										
										
											2009-10-26 08:38:59 +01:00
										 |  |  |     This interface function unbind a thermal cooling device from the certain | 
					
						
							|  |  |  |     trip point of a thermal zone device. This function is usually called in | 
					
						
							|  |  |  |     the thermal zone device .unbind callback. | 
					
						
							|  |  |  |     tz: the thermal zone device | 
					
						
							|  |  |  |     cdev: thermal cooling device | 
					
						
							|  |  |  |     trip: indicates which trip point the cooling devices is associated with | 
					
						
							|  |  |  | 	  in this thermal zone. | 
					
						
							| 
									
										
										
										
											2008-01-17 15:51:08 +08:00
										 |  |  | 
 | 
					
						
							|  |  |  | 2. sysfs attributes structure | 
					
						
							|  |  |  | 
 | 
					
						
							|  |  |  | RO	read only value | 
					
						
							|  |  |  | RW	read/write value | 
					
						
							|  |  |  | 
 | 
					
						
							| 
									
										
										
										
											2008-04-22 08:50:09 +08:00
										 |  |  | Thermal sysfs attributes will be represented under /sys/class/thermal. | 
					
						
							|  |  |  | Hwmon sysfs I/F extension is also available under /sys/class/hwmon | 
					
						
							|  |  |  | if hwmon is compiled in or built as a module. | 
					
						
							| 
									
										
										
										
											2008-01-17 15:51:08 +08:00
										 |  |  | 
 | 
					
						
							|  |  |  | Thermal zone device sys I/F, created once it's registered: | 
					
						
							| 
									
										
										
										
											2008-04-22 08:50:09 +08:00
										 |  |  | /sys/class/thermal/thermal_zone[0-*]: | 
					
						
							| 
									
										
										
										
											2009-10-26 08:38:59 +01:00
										 |  |  |     |---type:			Type of the thermal zone | 
					
						
							|  |  |  |     |---temp:			Current temperature | 
					
						
							|  |  |  |     |---mode:			Working mode of the thermal zone | 
					
						
							|  |  |  |     |---trip_point_[0-*]_temp:	Trip point temperature | 
					
						
							|  |  |  |     |---trip_point_[0-*]_type:	Trip point type | 
					
						
							| 
									
										
										
										
											2008-01-17 15:51:08 +08:00
										 |  |  | 
 | 
					
						
							|  |  |  | Thermal cooling device sys I/F, created once it's registered: | 
					
						
							| 
									
										
										
										
											2008-04-22 08:50:09 +08:00
										 |  |  | /sys/class/thermal/cooling_device[0-*]: | 
					
						
							| 
									
										
										
										
											2009-10-26 08:38:59 +01:00
										 |  |  |     |---type:			Type of the cooling device(processor/fan/...) | 
					
						
							|  |  |  |     |---max_state:		Maximum cooling state of the cooling device | 
					
						
							|  |  |  |     |---cur_state:		Current cooling state of the cooling device | 
					
						
							| 
									
										
										
										
											2008-01-17 15:51:08 +08:00
										 |  |  | 
 | 
					
						
							|  |  |  | 
 | 
					
						
							| 
									
										
										
										
											2009-10-26 08:38:59 +01:00
										 |  |  | Then next two dynamic attributes are created/removed in pairs. They represent | 
					
						
							|  |  |  | the relationship between a thermal zone and its associated cooling device. | 
					
						
							|  |  |  | They are created/removed for each successful execution of | 
					
						
							|  |  |  | thermal_zone_bind_cooling_device/thermal_zone_unbind_cooling_device. | 
					
						
							| 
									
										
										
										
											2008-01-17 15:51:08 +08:00
										 |  |  | 
 | 
					
						
							| 
									
										
										
										
											2009-10-26 08:38:59 +01:00
										 |  |  | /sys/class/thermal/thermal_zone[0-*]: | 
					
						
							|  |  |  |     |---cdev[0-*]:		[0-*]th cooling device in current thermal zone | 
					
						
							|  |  |  |     |---cdev[0-*]_trip_point:	Trip point that cdev[0-*] is associated with | 
					
						
							| 
									
										
										
										
											2008-01-17 15:51:08 +08:00
										 |  |  | 
 | 
					
						
							| 
									
										
										
										
											2008-04-22 08:50:09 +08:00
										 |  |  | Besides the thermal zone device sysfs I/F and cooling device sysfs I/F, | 
					
						
							| 
									
										
										
										
											2009-10-26 08:38:59 +01:00
										 |  |  | the generic thermal driver also creates a hwmon sysfs I/F for each _type_ | 
					
						
							|  |  |  | of thermal zone device. E.g. the generic thermal driver registers one hwmon | 
					
						
							|  |  |  | class device and build the associated hwmon sysfs I/F for all the registered | 
					
						
							|  |  |  | ACPI thermal zones. | 
					
						
							|  |  |  | 
 | 
					
						
							| 
									
										
										
										
											2008-04-22 08:50:09 +08:00
										 |  |  | /sys/class/hwmon/hwmon[0-*]: | 
					
						
							| 
									
										
										
										
											2009-10-26 08:38:59 +01:00
										 |  |  |     |---name:			The type of the thermal zone devices | 
					
						
							|  |  |  |     |---temp[1-*]_input:	The current temperature of thermal zone [1-*] | 
					
						
							|  |  |  |     |---temp[1-*]_critical:	The critical trip point of thermal zone [1-*] | 
					
						
							|  |  |  | 
 | 
					
						
							| 
									
										
										
										
											2008-04-22 08:50:09 +08:00
										 |  |  | Please read Documentation/hwmon/sysfs-interface for additional information. | 
					
						
							| 
									
										
										
										
											2008-01-17 15:51:08 +08:00
										 |  |  | 
 | 
					
						
							|  |  |  | *************************** | 
					
						
							|  |  |  | * Thermal zone attributes * | 
					
						
							|  |  |  | *************************** | 
					
						
							|  |  |  | 
 | 
					
						
							| 
									
										
										
										
											2009-10-26 08:38:59 +01:00
										 |  |  | type | 
					
						
							|  |  |  | 	Strings which represent the thermal zone type. | 
					
						
							|  |  |  | 	This is given by thermal zone driver as part of registration. | 
					
						
							|  |  |  | 	E.g: "acpitz" indicates it's an ACPI thermal device. | 
					
						
							|  |  |  | 	In order to keep it consistent with hwmon sys attribute; this should | 
					
						
							|  |  |  | 	be a short, lowercase string, not containing spaces nor dashes. | 
					
						
							|  |  |  | 	RO, Required | 
					
						
							|  |  |  | 
 | 
					
						
							|  |  |  | temp | 
					
						
							|  |  |  | 	Current temperature as reported by thermal zone (sensor). | 
					
						
							|  |  |  | 	Unit: millidegree Celsius | 
					
						
							|  |  |  | 	RO, Required | 
					
						
							|  |  |  | 
 | 
					
						
							|  |  |  | mode | 
					
						
							|  |  |  | 	One of the predefined values in [kernel, user]. | 
					
						
							|  |  |  | 	This file gives information about the algorithm that is currently | 
					
						
							|  |  |  | 	managing the thermal zone. It can be either default kernel based | 
					
						
							|  |  |  | 	algorithm or user space application. | 
					
						
							|  |  |  | 	kernel	= Thermal management in kernel thermal zone driver. | 
					
						
							|  |  |  | 	user	= Preventing kernel thermal zone driver actions upon | 
					
						
							|  |  |  | 		  trip points so that user application can take full | 
					
						
							|  |  |  | 		  charge of the thermal management. | 
					
						
							|  |  |  | 	RW, Optional | 
					
						
							|  |  |  | 
 | 
					
						
							|  |  |  | trip_point_[0-*]_temp | 
					
						
							|  |  |  | 	The temperature above which trip point will be fired. | 
					
						
							|  |  |  | 	Unit: millidegree Celsius | 
					
						
							|  |  |  | 	RO, Optional | 
					
						
							|  |  |  | 
 | 
					
						
							|  |  |  | trip_point_[0-*]_type | 
					
						
							|  |  |  | 	Strings which indicate the type of the trip point. | 
					
						
							|  |  |  | 	E.g. it can be one of critical, hot, passive, active[0-*] for ACPI | 
					
						
							|  |  |  | 	thermal zone. | 
					
						
							|  |  |  | 	RO, Optional | 
					
						
							|  |  |  | 
 | 
					
						
							|  |  |  | cdev[0-*] | 
					
						
							|  |  |  | 	Sysfs link to the thermal cooling device node where the sys I/F | 
					
						
							|  |  |  | 	for cooling device throttling control represents. | 
					
						
							|  |  |  | 	RO, Optional | 
					
						
							|  |  |  | 
 | 
					
						
							|  |  |  | cdev[0-*]_trip_point | 
					
						
							|  |  |  | 	The trip point with which cdev[0-*] is associated in this thermal | 
					
						
							|  |  |  | 	zone; -1 means the cooling device is not associated with any trip | 
					
						
							|  |  |  | 	point. | 
					
						
							|  |  |  | 	RO, Optional | 
					
						
							| 
									
										
										
										
											2009-10-26 08:39:00 +01:00
										 |  |  | 
 | 
					
						
							|  |  |  | passive | 
					
						
							|  |  |  | 	Attribute is only present for zones in which the passive cooling | 
					
						
							|  |  |  | 	policy is not supported by native thermal driver. Default is zero | 
					
						
							|  |  |  | 	and can be set to a temperature (in millidegrees) to enable a | 
					
						
							|  |  |  | 	passive trip point for the zone. Activation is done by polling with | 
					
						
							|  |  |  | 	an interval of 1 second. | 
					
						
							|  |  |  | 	Unit: millidegrees Celsius | 
					
						
							| 
									
										
										
										
											2009-10-26 08:39:02 +01:00
										 |  |  | 	Valid values: 0 (disabled) or greater than 1000 | 
					
						
							| 
									
										
										
										
											2009-10-26 08:39:00 +01:00
										 |  |  | 	RW, Optional | 
					
						
							| 
									
										
										
										
											2009-10-26 08:38:59 +01:00
										 |  |  | 
 | 
					
						
							|  |  |  | ***************************** | 
					
						
							|  |  |  | * Cooling device attributes * | 
					
						
							|  |  |  | ***************************** | 
					
						
							|  |  |  | 
 | 
					
						
							|  |  |  | type | 
					
						
							|  |  |  | 	String which represents the type of device, e.g: | 
					
						
							|  |  |  | 	- for generic ACPI: should be "Fan", "Processor" or "LCD" | 
					
						
							|  |  |  | 	- for memory controller device on intel_menlow platform: | 
					
						
							|  |  |  | 	  should be "Memory controller". | 
					
						
							|  |  |  | 	RO, Required | 
					
						
							|  |  |  | 
 | 
					
						
							|  |  |  | max_state | 
					
						
							|  |  |  | 	The maximum permissible cooling state of this cooling device. | 
					
						
							|  |  |  | 	RO, Required | 
					
						
							|  |  |  | 
 | 
					
						
							|  |  |  | cur_state | 
					
						
							|  |  |  | 	The current cooling state of this cooling device. | 
					
						
							|  |  |  | 	The value can any integer numbers between 0 and max_state: | 
					
						
							|  |  |  | 	- cur_state == 0 means no cooling | 
					
						
							|  |  |  | 	- cur_state == max_state means the maximum cooling. | 
					
						
							|  |  |  | 	RW, Required | 
					
						
							| 
									
										
										
										
											2008-01-17 15:51:08 +08:00
										 |  |  | 
 | 
					
						
							|  |  |  | 3. A simple implementation | 
					
						
							|  |  |  | 
 | 
					
						
							| 
									
										
										
										
											2009-10-26 08:38:59 +01:00
										 |  |  | ACPI thermal zone may support multiple trip points like critical, hot, | 
					
						
							|  |  |  | passive, active. If an ACPI thermal zone supports critical, passive, | 
					
						
							|  |  |  | active[0] and active[1] at the same time, it may register itself as a | 
					
						
							|  |  |  | thermal_zone_device (thermal_zone1) with 4 trip points in all. | 
					
						
							|  |  |  | It has one processor and one fan, which are both registered as | 
					
						
							|  |  |  | thermal_cooling_device. | 
					
						
							|  |  |  | 
 | 
					
						
							|  |  |  | If the processor is listed in _PSL method, and the fan is listed in _AL0 | 
					
						
							|  |  |  | method, the sys I/F structure will be built like this: | 
					
						
							| 
									
										
										
										
											2008-01-17 15:51:08 +08:00
										 |  |  | 
 | 
					
						
							|  |  |  | /sys/class/thermal: | 
					
						
							|  |  |  | 
 | 
					
						
							|  |  |  | |thermal_zone1: | 
					
						
							| 
									
										
										
										
											2009-10-26 08:38:59 +01:00
										 |  |  |     |---type:			acpitz | 
					
						
							|  |  |  |     |---temp:			37000 | 
					
						
							|  |  |  |     |---mode:			kernel | 
					
						
							|  |  |  |     |---trip_point_0_temp:	100000 | 
					
						
							|  |  |  |     |---trip_point_0_type:	critical | 
					
						
							|  |  |  |     |---trip_point_1_temp:	80000 | 
					
						
							|  |  |  |     |---trip_point_1_type:	passive | 
					
						
							|  |  |  |     |---trip_point_2_temp:	70000 | 
					
						
							|  |  |  |     |---trip_point_2_type:	active0 | 
					
						
							|  |  |  |     |---trip_point_3_temp:	60000 | 
					
						
							|  |  |  |     |---trip_point_3_type:	active1 | 
					
						
							|  |  |  |     |---cdev0:			--->/sys/class/thermal/cooling_device0 | 
					
						
							|  |  |  |     |---cdev0_trip_point:	1	/* cdev0 can be used for passive */ | 
					
						
							|  |  |  |     |---cdev1:			--->/sys/class/thermal/cooling_device3 | 
					
						
							|  |  |  |     |---cdev1_trip_point:	2	/* cdev1 can be used for active[0]*/ | 
					
						
							| 
									
										
										
										
											2008-01-17 15:51:08 +08:00
										 |  |  | 
 | 
					
						
							|  |  |  | |cooling_device0: | 
					
						
							| 
									
										
										
										
											2009-10-26 08:38:59 +01:00
										 |  |  |     |---type:			Processor | 
					
						
							|  |  |  |     |---max_state:		8 | 
					
						
							|  |  |  |     |---cur_state:		0 | 
					
						
							| 
									
										
										
										
											2008-01-17 15:51:08 +08:00
										 |  |  | 
 | 
					
						
							|  |  |  | |cooling_device3: | 
					
						
							| 
									
										
										
										
											2009-10-26 08:38:59 +01:00
										 |  |  |     |---type:			Fan | 
					
						
							|  |  |  |     |---max_state:		2 | 
					
						
							|  |  |  |     |---cur_state:		0 | 
					
						
							| 
									
										
										
										
											2008-04-22 08:50:09 +08:00
										 |  |  | 
 | 
					
						
							|  |  |  | /sys/class/hwmon: | 
					
						
							|  |  |  | 
 | 
					
						
							|  |  |  | |hwmon0: | 
					
						
							| 
									
										
										
										
											2009-10-26 08:38:59 +01:00
										 |  |  |     |---name:			acpitz | 
					
						
							|  |  |  |     |---temp1_input:		37000 | 
					
						
							|  |  |  |     |---temp1_crit:		100000 |